Search in Category
Categories
Shop All Emergency Eye Care - Eyewash Stations
Honeywell Porta Stream Replacement Eyewash Concentrate
Honeywell Porta Stream Eyewash Station
Don't see what you need?
Click here to let us know and we'll help you find what you're looking for.Emergency Eye Care and Eyewash Stations
When a chemical, dust, or particulate reaches the eye, the first 15 seconds decide the outcome. Buy portable and plumbed eyewash stations, eyewash solution, eyewash concentrate, eye cups, and eye pads from Honeywell, Guardian, Haws, Speakman, Medique, Bausch & Lomb, and Dynarex. Everything ships from our Auburn, Massachusetts warehouse to job sites across New England with no order minimums.
|
An emergency eyewash station delivers a controlled flush of sterile saline or potable water to the eyes after chemical, dust, or particulate exposure. ANSI Z358.1 calls for eyewash within 10 seconds travel time of the hazard, delivering a 15 minute continuous flush at a tepid temperature. |
ANSI/ISEA Z358.1 governs emergency eyewash and shower equipment in the United States. It calls for eyewash equipment within 10 seconds travel time of any location where the eyes may be exposed to corrosive or injurious materials, reachable on an unobstructed path, delivering a continuous 15 minute flush. OSHA 29 CFR 1910.151(c) requires suitable facilities for quick drenching or flushing of the eyes wherever corrosive materials are present, and inspectors reference ANSI Z358.1 as the benchmark for what suitable means.
Plumbed eyewash stations connect to a facility water supply and deliver the sustained 15 minute flush with no refill cycle, making them the correct specification for fixed workstations with permanent chemical exposure. Portable eyewash stations use a self-contained sealed reservoir and are the answer for job sites, remote work areas, and locations without plumbing. Portable units require a bacteriostatic preservative such as Guardian Aquasep eyewash water preservative and a defined replacement schedule to keep the solution within service life. Restock cartridge units with replacement eyewash cartridges.
Personal eyewash bottles are a supplement, not a substitute. A Honeywell Eyesaline 32oz emergency eyewash station or the dual-bottle 32oz configuration provides immediate flushing at the point of injury while the worker moves toward a primary station capable of the full 15 minutes. Compact options including the Medi-First 16oz eyewash, Bausch & Lomb 4oz eyewash with eye cup, and Dynarex sealed vial eye cups belong in vehicles, tool cribs, and first aid kits. Pair every eyewash program with safety glasses and face shields, because preventing the exposure beats flushing after it.
|
Plumbed and Portable Stations Plumbed units for fixed workstations with permanent chemical exposure. Sealed-reservoir portable stations for job sites and remote areas without plumbing access. Both stocked and ready to ship. |
|
Honeywell, Guardian, Haws and Speakman Stocked from the manufacturers specified in industrial eyewash programs, plus eyewash solution, concentrate, preservative, eye cups, and eye pads for ongoing station maintenance. |
|
Built Around ANSI Z358.1 Station types, flush duration, and placement guidance aligned to the ANSI Z358.1 requirement for eyewash within 10 seconds travel time delivering a 15 minute continuous flush. |
Choosing the Right Eyewash Station
| Station Type | Water Source | Flush Duration | Best Application | Maintenance |
| Plumbed eyewash station | Facility potable water | Continuous 15 min | Fixed workstations, labs, chemical handling areas | Weekly activation test |
| Portable eyewash station | Sealed reservoir | 15 min per ANSI unit | Job sites, remote areas, no plumbing available | Solution and preservative replacement |
| Personal eyewash bottle | Sealed bottle | Immediate flush only | Vehicles, tool cribs, supplemental point-of-use | Replace at expiration date |
| Eyewash concentrate | Mixed with water | Refills portable units | Restocking Porta-Stream and similar units | Mix per manufacturer ratio |
| Eye cups and eye pads | Single use | Single application | First aid kits, minor irrigation and covering | Replace after any use |
Frequently Asked Questions
1. How close does an eyewash station need to be?
ANSI Z358.1 calls for eyewash equipment within 10 seconds travel time of the hazard, on an unobstructed path and on the same level where possible. That is roughly 55 feet of unobstructed walking distance for an injured worker who may not be able to see clearly.
2. How long should you flush your eyes after chemical exposure?
ANSI Z358.1 specifies a 15 minute continuous flush for most chemical exposures. Some strongly corrosive materials call for longer flushing, and the Safety Data Sheet for the specific chemical should always be consulted. Personal eyewash bottles cannot deliver 15 minutes and serve as a bridge to a primary station.
3. What is the difference between a plumbed and a portable eyewash station?
Plumbed stations connect to the facility water supply and deliver an uninterrupted flush with no refill cycle. Portable stations use a sealed self-contained reservoir and serve job sites and areas without plumbing. Both are stocked in emergency eye care.
4. Does eyewash solution expire?
Yes. Sealed eyewash solution and cartridges carry an expiration date and must be replaced when reached. Portable stations filled with potable water require a bacteriostatic preservative such as Guardian Aquasep and periodic solution replacement to prevent microbial growth.
5. How often should eyewash stations be tested?
ANSI Z358.1 calls for plumbed stations to be activated weekly to verify flow and clear the supply line of sediment and stagnant water. Portable stations should be inspected on the manufacturer schedule to confirm fluid level, seal integrity, and solution expiration date.
6. Are personal eyewash bottles enough to meet ANSI Z358.1?
No. Personal eyewash bottles provide immediate flushing at the point of injury but cannot deliver the 15 minute continuous flush ANSI requires. They are classified as supplemental equipment and must be paired with a primary plumbed or portable station.
7. What water temperature should an eyewash station deliver?
ANSI Z358.1 specifies tepid flushing fluid, generally understood as between 60 and 100 degrees Fahrenheit. Water that is too cold discourages a worker from completing the full 15 minute flush, and water that is too warm can accelerate chemical absorption into eye tissue.
8. Do eyewash stations need freeze protection in winter?
Outdoor and unheated locations in New England require freeze protection for both plumbed and portable equipment. A frozen station provides no protection. Verify the freeze rating and inspect seasonally before winter conditions arrive.
9. What are eye cups used for?
Eye cups provide a controlled single-use irrigation vessel for flushing minor debris from the eye. They are a first aid kit item for minor incidents and are not a substitute for an ANSI-compliant eyewash station where chemical or corrosive exposure is present.
10. What brands of eyewash stations does Masterman's carry?
Masterman's stocks emergency eye care from Honeywell, Guardian, Haws, Speakman, Medique, Bausch & Lomb, and Dynarex. Call 800-525-3313 to match station type and placement to your facility hazard assessment.